S3000 Range
38 models from 18 to 400 l/s
Principle of operation
Water is one of our most precious resources. Cooling towers
reduce the water consumption by 95% versus the out-dated "one through"
systems, by recycling the water. The heated water from the cooling process
is distributed over the wet deck surface, which serves as a heat exchanger.
As the air drawn through the cooling tower evaporates a small portion
of the recirculating water, heat will be removed from the remaining water.
The cooled water can then be pumped back to the heat load for another
cooling cycle.
Characteristics
- double crossflow
design
- induced draught
configuration
- horizontal air
entry from 2 sides
- vertical air discharge
- aluminium axial
fans
- gravity water distribution
- BACross film fill
with 19 mm spacing
- V-belt drive
Main
features
- high efficiency
thermal performance
- low fan power
- low operating
weight due to depressed sump section
- multi-cell arrangement
possible
- factory built
sections for minimum site assembly
- low maintenance
requirements
- suitable for
outdoor locations
|
 |
|
Material
options
Baltiplus corrosion protection
Baltiplus
Corrosion Protection comprises all steel components fabricated from Z
600 galvanised steel with 600 g of zinc per mē coating. Cut edges are
protected with a zinc rich paint. All fasteners have a 3-stage protective
coating consisting of a zinc phosphate treatment, a zinc rich inorganic
resin coating and an aluminium rich organic topcoat. The exterior surfaces
of the equipment are finished with a coat of polymeric zinc aluminium
paint. Baltiplus
corrosion protection water quality control guidelines. To achieve long
equipment life, the following limits of the circulating water quality
should not be exceeded:
Baltibond Corrosion Protection System
The BALTIBOND Corrosion Protection System is applied to individual galvanized
steel components prior to assembly. These components are manufactured
from Z 600 mill galvanized steel sheets with 600 g of zinc/mē. After manufacturing
the components undergo an industrial cleaning and drying pre-treatment
process. Immediately after the pre-treatment the components are electrostatically
coated with a dry, polymeric hybrid thermosetting powder. The coated components
are then put through a thermally activated curing process during which
the powder is fuse bonded to the substrate. Stringent quality control
procedures and regular testing during the coating process assure consistent
high quality of the protection system. The fasteners used for assembly
have a 3-stage protective coating comprising a zinc phosphate treatment,
a zinc rich inorganic resin coating and an aluminum rich organic top coat.
|